Power supply voltage |
100–240 V AC, 50/60 Hz |
Power consumption |
≤ 5 VA (at 100 V) or ≤ 6 VA (at 220 V) |
Input |
RTD (Pt100), thermocouples (9 types) |
Indication accuracy |
(±0.5% of indicated value or 1°C, whichever is larger) ±1 digit ±1°C |
Sampling rate |
0.2 s |
SV/PV correction |
Provided |
Control |
On-off, PID, fuzzy, two-degree-of-freedom PID control (Auto tuning is available except for on-off control.) |
Control output |
Relay contact output or SSR drive output In the dual control, the alarm output 1 functions as the control output 2. |
Alarm output |
1 or 2 (option) |
Alarm type |
absolute value, deviation value, zone, high, low, hold, alarm latch, excitation/non-excitation |
Burnout |
If burnout occurs, the output goes to high limit or low limit. |
Display |
7-segment 4-digit LED Process value and set value |
Loader interface |
Allows you to view and edit the parameter values on your PC. PXE can be bus-powered via the dedicated loader cable. |
Protection class of front panel |
NEMA-4X (equivalent to IP66) Only when mounted on panel by using the dedicated waterproof packing. |
Dimensions and weight |
48 (W) × 48 (H) × 63.5 (D) mm, approx. 100 g |
Mounting |
Panel mount (mounting fixture provided) |
Terminal |
M3 screw terminal |
Ambient temperature |
-10°C to +55℃ |